> MC > MG > MG31 > MS > MS31 > MS33 > SMK |
| |
|
| |
Features |
| |
• Line interactive design |
| |
• Boost and buck AVR (Auto voltage regulation) |
| |
• Fully digitized microprocessor controlled |
| |
• Smart LCD display |
| |
• Energy saving function (UPS sleep mode) |
| |
• 50/60Hz frequency auto sensing and selection |
| |
• On-battery startup (DC power on) |
| |
• Lightning and surge protection |
| |
• Short circuit and overload protection |
| |
• Advanced battery management (ABM technology) |
| |
• Smart RS-232 communication interface |
| |
• Tel/Modem internet surge suppression |
| |
• Site wiring fault warning (available on certain models only) |
| |
• Optional SNMP Adapter |
| |
|
| |
General Specifications* |
| |
Rated Power |
1KVA to 5KVA |
| |
|
| |
Input |
| |
Voltage |
100, 110, 115, 120, 220, 230 or 240VAC, single phase |
| |
Voltage range |
±25% |
| |
Frequency |
50 or 60 Hz ±5Hz (auto sensing) |
| |
Output |
| |
Voltage |
Typical as same as input, ±5% at battery mode |
| |
Voltage regulation |
+15% at 75% to 91% nominal input; |
| |
|
-13% at 109% to 125% nominal input |
| |
Frequency |
50Hz or 60Hz, auto-detecting; ±0.5% at battery mode |
| |
Waveform |
Pure sine wave |
| |
Power factor |
0.6 |
| |
Overload capacity |
>110%, shut down in 20s; |
| |
|
>125%, shut down in 5s. |
| |
Short circuit protection |
cut off output immediately or input fuse |
| |
Transfer time |
2 to 4ms |
| |
LCD display features |
Line/ battery / inverter status, operation mode, |
| |
|
input voltage & frequency, output voltage & frequency, |
| |
|
battery voltage, load capacity, fault |
| |
Battery & Charger |
| |
Battery type |
Sealed maintenance free (SMF) VRLA |
| |
Charging time |
4 hours typical to 90% capacity |
| |
Protection |
Auto self-test, discharge protection |
| |
|
Battery replacement indicator |
| |
Communication Interface |
| |
RS-232 |
Serial interface |
| |
Intelligent slot |
For installation of status monitoring module |
| |
Mechanical |
| |
Smart display |
input voltage, input frequency, output voltage, battery |
| |
|
voltage, load capacity and ambient temperature. |
| |
|
Operation mode, line, battery and inverter status |
| |
Environmental |
| |
Operating temperature |
0 to 40°C / 32 to 104°F |
| |
Storage temperature |
-25 to 55°C / -13 to 131°F |
| |
Operating humidity |
0 to 95% non-condensing |
| |
Elevation |
3500 meters / 11480 ft. (max.) |
| |
|
|
| |
* Please refer to Technical Datasheet for nominal specifications. |
| |
** Due to continuing improvements, design, layout, specifications and configuration of the product are subject to change without notice. |
| |
|
| |
Downloads |
| |
Technical Datasheet (A4 / PDF / 116KB) |